Precision Digital PD765 Process & Temperature Panel Meter

Shop Now

Features

  • 4-20 mA, plus or minus 10 V, TC and RTD Inputs
  • NEMA 4X, IP65 Front
  • Shallow Depth Case 3.6″ Behind Panel
  • Operating temperature range of between -40 C and 65 C
  • Universal Power Supply 85-265 VAC
  • Two Relays Option with Alternation and Time Delays
  • 4-20 mA Analog Output Option
  • 24 VDC at 200 mA Transmitter Power Option
  • RS-232, RS-485 Serial Communication Options
  • Free Modbus RTU Protocol & LabVIEW Driver
  • Sunlight Readable Display
  • Free MeterView Software Download

Summary

Thermal Devices is an authorized Precision Digital distributor and proudly offers the Precision Digital PD765 Process And Temperature Digital Panel Meter. The Trident PD765 digital panel meter is one of the most versatile meters on the market and will satisfy a wide variety of process and temperature applications. Housed in an 1/8 DIN enclosure with a NEMA 4X front, the meter can be field programmed to accept process voltage (0-5 V, 1-5 V, etc.) and current (4-20 mA) inputs, 100 Ohm RTDs, and the four most common thermocouples. The display height on the standard Trident meter is 0.56″ (14.2 mm) and on the Trident X2 the display height is an astounding 1.2″ (30.5 mm). The intensity of the display can be adjusted to compensate for various lighting conditions, including direct sunlight. Programming and setup can be performed with the four front panel pushbuttons, free MeterView software, or using the copy function. Options for the PD765 include 2 relays, a 4-20 mA output, 24 V transmitter power supply, and Modbus serial communications. Contact a Thermal Devices’ Sales Engineer for more information! Or, request a quote.

Product Description

Precision Digital PD765 Details:

Display: Trident: 0.56” (14.2 mm); Trident X2: 1.20” (30.5 mm) red LED, 4 digits (-1999 to 9999)
Display Intensity: Eight user selectable intensity levels
Front Panel: NEMA 4X, IP65; panel gasket provided
Programming Methods: Four front panel buttons, cloning with Copy feature, PC with MeterView or LabVIEW software, and Modbus registers. Certified LabVIEW driver available.
Noise Filter: Programmable 2 to 199 (0 will disable filter)
Display Update Rate: Process/RTD: 3.7-5/sec; TC: 1.8-2.5/sec
Overrange: Display flashes 9999
Underrange: Display flashes -1999
Recalibration: All inputs are calibrated at the factory; recalibration is recommended at least every 12 months.
Max/Min Display: Stored until reset by user or meter is turned off.
Password: Restricts modification of programmed settings.
Non-Volatile Memory: Settings stored for a minimum of 10 years.
Power Options: 85-265 VAC, 50/60 Hz; 90-265 VDC, 20 W max or 12-36 VDC; 12-24 VAC, 6 W max.
Required Fuse: UL Recognized, 5 A max, slow-blow; up to 6 meters may share one fuse.
Normal Mode Rejection: 64 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line; 500 V input-to-output or output-to-24 VDC supplies.
-6R5 & -6X5 models only: 100 V output-to-24 VDC supply
Operating Temperature: -40 to 65°C
Storage Temperature: -40 to 85°C
Relative Humidity: 0 to 90% non-condensing
Connections:
Power & Signal: removable screw terminal blocks accept 12 to 22 AWG.
Serial: RJ11 header, standard on all meters.
Enclosure: 1/8 DIN, high impact plastic, 94V-0, color; gray
Weight: 9.5 oz (269 g) (including options)
UL File Number: E160849; 508 Industrial Control Equipment