Trasor T/A/32SQ3100/305/1418/208/04/S142LY Type KNL MI Heating Cable

The Trasor T/A/32SQ3100/305/1418/208/04/S142LY Type KNL MI Heating Cable from Thermal Devices. 300V 2-conductor mineral insulated heating cable with Alloy 825 stainless sheath, Form A, 305 ft heated length, 1418W at 208V, with 4 ft S142LY cold lead.

Custom lengths, wattages, and configurations are available. Call (301) 831-7550 or email [email protected] to order the configuration your application requires.

$0.00

SKU: T/A/32SQ3100/305/1418/208/04/S142LY
SKU: T/A/32SQ3100/305/1418/208/04/S142LY Category:

Product Documentation

Trasor T/A/32SQ3100/305/1418/208/04/S142LY Type KNL MI Heating Cable

The Trasor T/A/32SQ3100/305/1418/208/04/S142LY is a Type KNL 300V, 2-conductor mineral insulated (MI) heating cable with an Alloy 825 stainless sheath, configured as a Form A heater: 305 ft heated length, 1418W at 208V (4.6 W/ft), with a 4 ft S142LY cold lead.

MI cable is ideal for high power industrial and commercial heating applications. The stainless Alloy 825 sheath has excellent resistance to corrosive salts and chemicals, and the cable is totally inorganic and will not deteriorate with age. Series resistance conductors provide constant wattage output along the entire length of the heater, and high temperature conductors allow operation at higher watt densities than other cables. All heating cables are factory fabricated to a specific length and rigorously tested to IEEE standards.

Specifications

Catalog Number T/A/32SQ3100/305/1418/208/04/S142LY
Heater Form Form A (Two Conductor)
Cable Size 32SQ3100
Resistance 0.1 Ω/ft
Cable O.D. 0.190″
Heated Length 305 ft
Wattage 1418W
Voltage 208V
Cold Lead S142LY, 4 ft
Sheath Material Alloy 825 stainless
Insulation Magnesium oxide
Maximum Operating Voltage 300V
Maximum Exposure Temperature 1100°F

Applications

  • Process pipe heating
  • Freeze protection
  • Snow melting
  • Asphalt heating
  • Frost heave protection
  • Tank and vessel heating

Custom lengths, wattages, and configurations are available. Call (301) 831-7550 or email [email protected] to order the configuration your application requires.

Trasor T/A/32SQ3100/305/1418/208/04/S142LY Type KNL MI Heating Cable

Form

A

Cable Size

32SQ3100

Current

6.8A

Volts

208V

Wattage

1418W

Heated Length

305 ft

Cold Lead

S142LY, 4 ft